[knowledge] fabrication technology of ship electrical prefabricated parts

Technological requirements for prefabricated parts technologyofcablepenetration1 and cable penetration cabletransit.

If there is no special indication in the tray table, the material of the penetration is ordinary grade a steel.

After the penetration is made, the sharp edges and burrs shall be polished, and anti-corrosion treatment shall be carried out.

Generally, it shall be coated with two layers of antirust primer.

Thematerialofpenetrationisordinarysteel(classA)ingenerally,ifnospecify.

Thetransitshouldbegrinded,andcoatingtwolayers.

Common cable penetration (without fire prevention and watertight requirements) is shown in the following figure 1 ordinarytransit (no fire proof no watertight) seedrawing1 1.1 representation of horizontalordinarytransit of ordinary cable frame express: DKL × B × H ×δ DK — ordinary cable frame horizontalordinarytransit1 2.

See Figure 1 below for ordinary cable drum (without fire prevention and water tightness requirements).

Verticalordinarytransit(no-fireproofno-watertight)seedrawing1.

Express: DTL × B × H ×δ DT — ordinary cable drum vertical ordinarytransitl – length B – width H – height high δ— The small ordinary cable frame and barrel with thickness can be pressed with galvanized pipe instead.

Miniordinarytransitscanbetakenplacedbypressedgalvanizedtube.

1.3 fire proof cable frame express: awnl × B × two hundred and fifty ×δ Aw — fire proof cable frame fire proof horizontal transit L – length B – width h eight — 250mm δ— Plate thickness thicknessn – see the following table for the fire resistance rating.

The height of seefollowable cable frame is fixed as theisfixed: 250mm type parameter type name fire resistance rating fireproofinggrade site aw1dmt-w watertight grade A-60 fire resistant cable frame dmt-wwatertightgrade A-60 fire proofingtransita-60, A-30, A-15 bulkhead bulkhead aw3dmt-w watertight class A-0 fire-resistant cable frame dmt-wwatertightgrade a-0fireproofingtransita-0 bulkhead bulkhead mark example signature: awn — type serial number fire proofgrade (the filling hole and vent hole are on both sides of the bulkhead) the specific requirements are shown in Figure 2: generally, the fire-resistant cable frame shown in Figure 2 is selected.

Double sided fire-resistant cable frame (perfectionholeandventilateholeintwosides), see: drawing2: internally, thisindoffire prooftransitville prioritized (seedrawing2), FIG.

2aw1, 3.

In order to ensure the necessary bending radius of the cable, in some special areas, the single-sided fire-resistant cable frame as shown in Fig.

3 can be selected (the filling hole and vent hole are on the same side of the bulkhead)..